Gingoog Electric Trading (G.E.T.) ™

October 2, 2009

DANFOSS Softstarter Comparison Table B

Filed under: GET MCD-100 series — Ralf @ 12:52 AM

 

Danfoss Softstarter Comparison Part 2


Now this Danfoss Softstarters are really great stuff, come with state of the art technologies in compact solutions and include features and protective functions just as you need it.

The following quick overview in form of an easy table gives you a perfect idea about the capabilities of each model and will surely assist you a good way in your further selections.

However, and I guess we got already a little bit used to these hosting limitations; we have to split this again into two sections.

Here now part 2:


Type MCD-100 MCD-201 MCD-202 MCD-500

Protection     Motor overload.

Adjustable trip class.

Excess start time.

Reverse phase rotation.

Motor thermistor input.

Shorted SCR-no start

Supply fault-no start.

Instantaneous overload.

As MCD-202 plus

Undercurrent.

Current Imbalance.

Starter over temperature.

Restart delay.

Warning before trips.

Adjustable phase

imbalance sensitivity.

Programmable input trip.

Individual phase loss trips.

Individual shorted SCR trips.

Integrated bypass relay overload.

Integrated bypass relay fail.

Fully adjustable protection.

Network communication timeout.

Heatsink overtemperature.

Battery/clock failure.

Supply frequency.

External trip.


Outputs   One output relay.

Line contactor control.

Two output relays.

Line contactor control.

Run contactor or trip function.

Three output relays.

Programmable output relay.

Programmable analogue output.

Motor thermistor.

         

Control Universal two wire control.

Programmable via 3 rotary switches.

Two or three wire control.

Programmable via 3 rotary switches.

Reset push button.

Two or three wire control.

Programmable via 3 rotary switches.

Reset push button.

8 language graphical display and key pad.

Quick Menu and Application Menu.

Buttons for Start, Stop, Reset and Remote Control.


Options   Modules for serial communication.

Remote operator kit.

PC software.

Modules for serial communication.

Remote operator kit.

PC software.

Modules for serial communication.

Remote operator kit.

PC software.


Others Extremely robust SCR.

Design for unlimited number of starts per hour.

LED indication.

IP20 enclosure.

Integral SCR bypass for minimum physical size and heat dissipation during nominal operation.

LED status indication

IP20 enclosure up to 55KW.

IP00 enclosure rated above.

Protection kit available.

Integral SCR bypass for minimum physical size and heat dissipation during nominal operation.

LED status indication

IP20 enclosure up to 55KW.

IP00 enclosure rated above.

Protection kit available.

Built in bypass function up to 110KW.

Configurable busbars for 360A and up.

Operation timers.

Jog, slow speed operation.

Auto reset of fault situations.

Emergency run (fire model).

99 event log.

Trip log.

User programmable metering and monitoring.

Simulation before connecting line voltage.


Find much more information in our MCD-100 folder

and visit also our complete GET Sky Drive Section

We certainly do hope that you enjoyed again the read and that you stay with us for more upcoming technical reading pleasure.

Retrieve our GET Contact Details  or send us your E-mail inquiry through the GET Contact Form.

Ralf Wabersich

Gingoog Electric Trading (G.E.T.)

DANFOSS Softstarter Comparison Table A

Filed under: GET MCD-100 series — Ralf @ 12:48 AM

 

Danfoss Softstarter Comparison Part 1


Now this Danfoss Softstarters are really great stuff, come with state of the art technologies in compact solutions and include features and protective functions just as you need it.

The following quick overview in form of an easy table gives you a perfect idea about the capabilities of each model and will surely assist you a good way in your further selections.

However, and I guess we got already a little bit used to these hosting limitations, we have to split this again into two sections.

Here now part 1:


Type MCD-100 MCD-201 MCD-202 MCD-500

Intro A true fit and forget Softstarter for DIN Rail mount.

It provides basic soft start and soft stop functions.

A physically compact Softstarter providing basic soft start and soft stop functionality. Physically similar to MCD-201 but providing enhanced soft start functionality and various motor protection features. The total motor starter solution provides advanced control methods for starting and stopping plus protection of both motor and application.

Concept Soft start.

Soft stop.

0.1KW to 11KW.

208 to 600VAC mains supply.

24 to 480V AC/DC control voltage

.

2 phase SCR control.

Soft start.

Soft stop.

7.5KW to 110KW

.

200 to 575VAC 

mains supply.

110 to 440VAC or

24V AC/DC control supply.

2 phase SCR control.

Current limit start.

Soft stop.

Motor protection.

200 to 575 VAC mains supply.

110 to 440VAC or

24V AC/DC control supply.

2 phase SCR control.

Enhanced soft start and soft stop

.

Motor and system protection.

21A to 1.6KA.

7.5KW to 800KW.

200 to 690VAC mains supply.

110 to 220VAC or 24V AC/DC control supply.

3 phase SCR control.


Start Timed voltage ramp up.

Adjustable start torque.

Selectable kick start function.

Timed voltage ramp up.

Adjustable initial torque.

Current limit start.

Initial current ramp up.

Adaptive Acceleration Control AAC.

Current Limit Start.

Current Ramp Start.

Dual parameter function.

Kick Start and Jog.


Stop Timed voltage ramp down. Timed voltage ramp down. Timed voltage ramp down. Adaptive Deceleration Control ADC.

TVR Soft Stop, timed voltage ramp.

Coast to stop.

DC brake function.

Soft brake function.

Jog function.


Find much more information in our MCD-100 folder

and visit also our complete GET Sky Drive Section

We certainly do hope that you enjoyed again the read and that you stay with us for more upcoming technical reading pleasure.

Retrieve our GET Contact Details  or send us your E-mail inquiry through the GET Contact Form.

Ralf Wabersich

Gingoog Electric Trading (G.E.T.)

September 6, 2009

MCD-100 features and benefits

Filed under: GET MCD-100 series — Ralf @ 3:11 AM

Danfoss VLT Softstarter MCD-100



  

 


The MCD-100 series is the most cost effective and extremely compact Softstarter solution for motors up to 11KW due to a very unique semiconductor design.

MCD-100 is a true “fit and forget” product. Selection can be simply made on the basis of the motor power, exactly as with traditional contactors.

MCD-100 products provide timed voltage ramp up and voltage ramp down. Ramp times can be individually adjusted easily with rotary switches from 0.4 to 10 seconds.

The starting torque can be also adjusted from 0 to 85% of the direct online (D.O.L.) torque.

This little babies are a perfect match for all smaller sized standard applications such as but not limited to pumps, fans, compressors, mixers, conveyors and of course many more.

The power range is clearly defined to be 1.5KW or below with the use of the MCD-100-001, 7.5KW and below with the model MCD-100-007 and a maximum of 11KW with the version MCD-100-011.

All members of the MCD-100 family are available for a variety of voltage applications ranging up to 600VAC.

Here a highlight summary of MCD-500 features and its benefits.  

Aside from the very well known and appreciated user friendliness we enjoy:


Small footprint and compact size saves panel space.

 


Selection can be based on the motor power to ease the choice.

Universal control voltage simplifies the selection even further and keeps replacement stock for maintenance reasons at an ultimate minimum.


“Fit and forget” contactor design simplifies likewise the installation and reduces also the required panel space.


Maximum reliability result into a maximum up time.


Robust semiconductor design achieves a reliable operation.


The feature of almost unlimited number of starts per hour without derating give you the maximum flexibility you do need at times.


Maximum ambient temperature of 50 degrees Celsius without derating eliminates the need for external cooling.


Very user friendly solutions to save commissioning time to ease the installation and to simplify the operation.


Digitally controlled rotary switches secure precise settings and simplify also here not only the installation but also the operation.


Easy DIN Rail mounting for sizes up to 30KW saves not only time but also space. 


Find much more information in our MCD-100 folder

and visit also our complete GET Sky Drive Section

We certainly do hope that you enjoyed again the read and that you stay with us for more upcoming technical reading pleasure.

Retrieve our GET Contact Details  or send us your E-mail inquiry through the GET Contact Form.

Ralf Wabersich

Gingoog Electric Trading (G.E.T.)

DANFOSS Softstarters

Filed under: GET MCD-100 series — Ralf @ 2:19 AM

 
Soft starts protect gear, goods, equipment and environment

 After the completion of the MCD-200 category some moments ago I would like to round up the Danfoss Softstarter stories now with the MCD-100 series, the smallest of all Danfoss Softstarter series which is perfect for all the simple applications using 25A and below.

Before going into more details let us recall again together what Softstarters are about. We spoke already about this product range in the GET Softstarters category but let us just quickly refresh our minds again:

An AC motor in general switched directly on to the mains power supply will ultimately struggle to reach its nominal speed as quick as possible.

This draws maximum current from the power supply and accelerates the application with its maximum torque and depending on the particular application, this can cause different problems.

Applications like pumps, conveyers, centrifuges and bandsaws must be started slowly to prevent mechanical shocks such as water hammer and strains on bands, couplings and shafts.

Principle of a Phase Angle Control:  

A Softstarter is an electronic device that regulates the voltage to the motor and this provides a smooth transition from standstill to full speed operation of the application.

DANFOSS VLT Softstarters all use the principle of phase angle control, a back to back coupled thyristors ramp up of the motor voltage.

In some DANFOSS VLT Softstarters, current transformers measure the actual motor current, providing feedback for starting current control but also for numerous motor and application protection functions.

DANFOSS VLT Softstarters cover a comprehensive range:

Soft starting and soft stopping (equally important) can be controlled in a number of ways depending on the application.

Some applications require non linear voltage ramp up and the voltage ramp is therefore related to the actual current drawn. Conversely, a bandsaw as another classic example requires a quick stop function provided by a DC brake.

Then again, a number of applications require a kick-start torque for an instantaneous period of time, followed by a soft ramp up acceleration.

DANFOSS VLT Softstarters do cover all of these applications and much more!


Find much more information in our MCD-100 folder

and visit also our complete GET Sky Drive Section

We certainly do hope that you enjoyed again the read and that you stay with us for more upcoming technical reading pleasure.

Retrieve our GET Contact Details  or send us your E-mail inquiry through the GET Contact Form.

Ralf Wabersich

Gingoog Electric Trading (G.E.T.)

Create a free website or blog at WordPress.com.

%d bloggers like this: