VLT Micro Specifications
Mains Supply (L1, L2, L3)
| Supply Voltage | 1 X 200 – 240VAC +/- 10% |
| Supply Voltage | 3 X 200 – 240VAC +/- 10% |
| Supply Voltage | 3 X 380 – 480VAC +/- 10% |
Output Data (U, V, W)
| Output Voltage | 0 – 100% of supply voltage |
| Output Frequency | 0 – 200Hz in WC+ mode |
| Output Frequency | 0 – 400Hz in U/f mode |
| Switching on output | Unlimited |
| Ramp Times | 0.05 – 3600 seconds |
Digital Inputs
| Programmable Inputs | 5 |
| Logic | PNP or NPN |
| Voltage Level | 0 – 24VDC |
| Maximum voltage on input | 28VDC |
| Input Resistance Ri | Approximately 4kΩ |
Pulse Inputs
| Programmable Pulse Inputs | 1 |
| Voltage Level | 0 – 24VDC (PNP positive logic) |
| Pulse Input Accuracy (0.1 – 110kHz) | Maximum error: 0.1% of full scale |
| Pulse Input Frequency | 20 – 5000Hz |
Analogue Inputs
| Analogue Inputs | 2 |
| Modes | 1 current / 1 voltage or current |
| Voltage Level | 0 – 10V (scalable) |
| Current Level | 0 / 4 (scalable) |
Analogue Outputs
| Programmable Analogue Outputs | 1 |
| Current range at analogue output | 0/4 – 20 mA |
| Maximum load to common at analogue output | 500 Ω |
| Accuracy on analogue output | Maximum error: 0.1% of full scale |
On-Board Power Supply
| Output Voltage | 10.5 +/- 0.5VDC |
| Maximum Load (10VDC) | 15mA |
| Maximum Load (24VDC) | 130mA |
Relay Outputs
| Programmable Relay Outputs | 1 |
| Maximum Terminal Load | 240VAC, 2A |
Cable Lengths
| Maximum motor cable length
With screened (shielded) cables |
15m |
| Maximum motor cable length
With unscreened (unshielded) cables |
50m |
Surroundings / External
| Enclosure Rating | IP20 |
| VibrationTest | 0.7g |
| Maximum Relative Humidity | 5% – 95% (IEC721-3-3);
Class 3K3 Non- condensingduring operation |
| Aggressive Environment | (IEC 721-3-3); coated class 3C3 |
| Ambient Temperature | Maximum of 50 degrees Celsius |
| 24 hours Average | Maximum of 40 degrees Celsius |
Protection and features:
Electronic thermal motor protection against overload
Temperature monitoring of the heat sink protects the Drive from overheating
The Drive is protected against short circuits on motor terminals U, V, W
The Drive is protected against earth fault on motor terminals U, V, W
GET everything you need and GET it done today
Please find also much much more on the general Drive subject in the
It is precisely there where you will find much more information to the general subject plus much more specific referrals to very much related downloads.
When you prefer to view directly all the corresponding file folders you may also proceed directly to the FC-51 folder in our
We certainly do hope that you enjoyed again the read and that you stay with us for more upcoming technical reading pleasure.
Retrieve our GET Contact Details or send us your E-mail inquiry through the GET Contact Form.
Ralf Wabersich
Gingoog Electric Trading (G.E.T.)