Mains Supply (L1, L2, L3)
| Supply Voltage | 200 to 240VAC, +/- 10% |
| Supply Voltage | 380 to 480VAC, +/- 10% |
| Supply Voltage | 525 to 600VAC, +/- 10% |
| Supply Voltage | 525 to 690VAC, +/- 10% |
| Supply Frequency | 50/60Hz |
| True Power Factor | Above 0.9 |
| Switching on input supply (L1, L2, L3) | 1 to 2 times/min |
Output Data (U, V, W)
| Output Voltage | 0 to 100% of supply voltage |
| Switching on output | Unlimited |
| Ramp Times | 1 to 3600 sec. |
| Closed Loop | 0 to 132 Hz |
Digital Inputs
| Programmable Digital Inputs | 6 |
| Logic | PNP or NPN |
| Voltage Level | 0 to 24VDC |
| Thermistor Inputs | 1 |
Analogue Inputs
| Analogue Inputs | 2 |
| Modes | Voltage or Current |
| Voltage Level | 0 to 10VDC (scalable) |
| Current Level | 0/4 to 20mA (scalable) |
Pulse Inputs
| Programmable Pulse Inputs | 2 |
| Voltage Level | 0 to 24VDC (PNP positive logic) |
| Pulse Input Accuracy | 0.1 to 110 kHz |
| Utilize some of the digital inputs |
Analogue Outputs
| Programmable Analogue Outputs | 1 |
| Current range at analogue output | 0/4 to 20mA |
| Maximum load (24VDC) | 130mA |
Relay Outputs
| Programmable Relay Outputs
(240VAC), 2A, and 400VAC, 2A) |
2 |
Fieldbus Communication
| Standard built-in | FC Protocol
Modbus RTU |
| Optional | Profibus
DeviceNet Ethernet |
Temperature
| Ambient Temperature | Up to 55 degrees Celsius |
GET the real water expert and GET it done today
Please find also much much more on the general Drive subject in the
It is precisely there where you will find much more information to the general subject plus much more specific referrals to very much related downloads. When you prefer to view directly all the corresponding file folders you may also proceed directly to the FC-200 folder in our
We certainly do hope that you enjoyed again the read and that you stay with us for more upcoming technical reading pleasure.
Retrieve our GET Contact Details or send us your E-mail inquiry through the GET Contact Form.
Ralf Wabersich
Gingoog Electric Trading (G.E.T.)